    Online UPS Queen Star Series 10K-80KVA

    Power Range: 10K-80KVA (3ph in/3ph out)

    ● DSP + IGBT technology.
    ● Output power factor 0.8.
    ● Active power factor correction in all phases.
    ● Emergency power off function (EPO).

    Where to buy »

    Online UPS Queen Star Series 10K-80KVA  (3ph in/3ph out)


    Key Features

    • True double-conversion.
    • DSP technology guarantees high performance.
    • Output power factor 0.8.
    • Active power factor correction in all phases.
    • 50Hz/60Hz frequency converter mode.
    • Accepts dual-mains inputs.
    • Generator compatible.
    • SNMP+USB+RS-232 multiple communications.
    • 3-stage extendable charging design for optimized battery performance.
    • Adjustable battery numbers.
    • Maintenance bypass available.
    • Optional N+X parallel redundancy.


    User Guides

    User's Manual

    No upload!

    Brochure

    Brochure

    Technical Specification

    Model

    33Q10KL

    33Q 20KL

    33Q 30KL

    33Q 40KL

    33Q 60KL

    33Q 80KL

    Comments

    Input

    Input voltage

    Rated voltage

    380VAC/220VAC

    380VAC

    Phase

    three phase with ground

    Turn on voltage range

    120±5274±5VAC

    207±9475±9VAC

    Bypass voltage range

    60±5300±5VAC

    105±9518±9VAC

    Could be adjusted by software.

    Bypass

    low loss

    60VAC~220VAC(default 60VAC)

    105VAC~380VAC

    (default 105VAC)

    Bypass low comeback

    Low loss +5VAC

    Low loss +17VAC

    Bypass high loss

    220VAC~300VAC(default 300VAC)

    380VAC~475VAC

    (default 475VAC)

    Bypass high comeback

    High loss -5VAC

    High loss -17VAC

    Line low loss

    /comeback

    (120±5) VAC /(140±5) VAC

    (207±9) VAC /(242±9)VAC

    load≤50

    (140±5) VAC /(160±5) VAC

    (242±9) VAC /(276±9)VAC

    50%<load ≤90

    (160±5) VAC /(175±5) VAC

    (276±9) VAC /(302±9)VAC

    load90

    Line high loss/comeback

    (275±5)VAC/(260±5)VAC

    (475±9)VAC/(449±9)VAC

    Input frequency

    Rated frequency

    50Hz

    Frequency

    low loss

    (40~49) ±0.2Hz(default:46Hz)

    Could be adjusted by software.

    Frequency

    low comeback

    Frequency low loss +0.5Hz

    Frequency

    high loss

    (51~60)±0.2Hz(default:54Hz)

    Frequency high comeback

    Frequency high loss -0.5Hz

    Input power factor

    Input power factor

    > 0.99

    33Q 10-40KL:220VAC,full R load

    33Q 60-80KL: 380VAC,full R load

    Generator

    Support generator input

    Generator rating≥2*UPS rating

    Input current

    Rated current

    14A

    28A

    42A

    67A

    80A

    105A

    Input THDI

    <= 10%

    Output protection

    Rating protection

    32A

    Breaker

    50A

    Breaker

    60A

    Breaker

    80A

    Breaker

    100A

    Breaker

    125A

    Breaker

    Output power

    VA/watt

    10KVA/8KW

    20KVA/16KW

    30KVA/24KW

    40KVA/32KW

    60KVA/

    48KW

    80KVA/

    64KW

    Rated voltage

    220VAC

    380VAC

    Sine wave

    Voltage range

    200/208/220/230/240VAC

    345/359/380/397/415 VAC

    33Q 10-40KL: Could be adjusted by software. 10% derating for 208VAC/200VAC.

    33Q 60-80KL: Could be adjusted by software. 10% derating for 345VAC/359VAC.

    Voltage regulation

    ±1%

    Voltage distortion

    ≤5

    ≤10

    Full RCD load

    ≤3

    Full R load

    DC offset

    ≤200mV

    Transient response

    ≤9

    R load 0%~100%~0

    ≤6

    R load 20%~100%~20

    Transient recovery

    ≤60ms voltage recovery to 90%

    Full RCD load

    Bypass output

    before turn-on

    YES

    Crest ration

    3:1

    Output frequency range

    Normal mode

    1,Same as input frequency46Hz~54Hz

    2,50HzInput frequency>54Hz or Input frequency<46Hz)

    Battery mode

    (50±0.1) Hz

    Slew rate

    1 Hz/Sec

    Efficiency

    Normal  mode

    > 93%

    > 90%

    Battery mode

    > 90%

    > 90%

    Overload

    Normal mode

    /battery mode

    Overload warning only

    105%±5%≤load

    1minthen transfer to bypass and alarm.

    105%±5%

    30Sthen transfer to bypass and alarm.

    125%±5%

    300mS, then transfer to bypass and alarm.

    load>150%±5%

    Automatically retransfer

    YES

    Short protection

    Normal/

    battery mode

    YES

    Transfer time

    Normal to battery mode

    0mS

    Battery to normal mode

    0mS

    Normal to bypass mode

    <4mS

    0mS

    Bypass to normal mode

    <4mS

    0mS

    Battery and charger

    Battery

    Rated voltage

    192VDC

    240VDC

    192VDC*2

    192VDC*2

    480VDC

    Type/Rating

    Battery quantity

    16

    20

    16*2

    16*2

    40

    Backup time

    Protection

    Low alarm voltage /comeback voltage

    (180.8V±4V)/ (188.8V±4V)

    (226V±4V)/ (236V±4V)

    (180.8V±4V)/ (188.8V±4V)

    (226V±4V)/ (236V±4V)

    (452V±4V)/ (472V±4V)

    33Q 30KL use two

    Shutdown voltage/ comeback voltage

    160V±4V/168V±4V

    (200V±4V)/ (210V±4V)

    160V±4V/

    168V±4V

    (200V±4V)/ (210V±4V)

    (400V±4V)/ (420V±4V)

    DC protection

    Overcharge protection/ comeback voltage

    (249.6V±4V)/

    (216V±4V)

    (312V±4V) (270V±4V)

    (249.6V±4V)/ (216V±4V)

    (312V±4V) (270V±4V)

    (624V±4V) (540V±4V)

    Leakage current

    < 500uA

    Over discharge protection

    14.5h

    Could be set by software

    Battery test

    Battery weak

    YES

    Battery fault

    YES

    Charger

    Output voltage

    (219.2±3)VDC

    (277±3)VDC

    (219.2±3)VDC

    (277±3)VDC

    (554±3)VDC

    Charge time

    Depends on the external battery capacity

    Charge current

    7.5A

    6A

    5A

    4A

    10A

    Interface

    Alarm silence

    YES

    DC power

    turn-on

    YES

    Automatically retransfer

    YES

    Audio alarm

    Battery mode

    Beep/4s

    Battery low/

    charger fault

    Beep/1s

    UPS fault

    Continue beep

    Overload

    Beep/1s

    Bypass mode

    Beep/2Min

    L/N inverse

    Beep/2Min

    Communication

    RS232 interface

    YES

    Intelligent slot

    YES

    Monitor software

    Appending with UPS

    Cooling

    Force air cooling

    Display

    LCD/LED displays UPS status

    Environment

    Work temperature

    0℃40℃

    Altitude

    1000m

    Audible noise

    ≤60dB

    Storage temperature

    15℃45℃

    Work humidity

    20%95

    Standard

    EMS

    ESD

    IEC61000-4-2

    Level4

    RS

    IEC61000-4-3

    Level3

    EFT

    IEC61000-4-4

    Level4

    Surge

    IEC61000-4-5

    Level4

    EMI

    Conducted

    EN55022

    Class A

    Radiated

    EN55022

    Class A

    Safety

    Safety

    GB4943-2001/IEC62040-1

    Machinery features

    Size

    Outline dimension and net weight

    L*W*H (mm)

    710*260*717

    840*515*1135

    Net weight(Kg)

    45/93

    50/98

    195

    208

    Optional functions

    60Hz

    Optional

    Set by software

    Converter mode

    Optional

    Set by software

    ECO

    Optional

    Optional

    Available and set by software

    EPO

    Optional

    Optional

    *Specification is subject to change without further notice



    Product Category Contact Us UPSEN
    • UPS Power
    • Inverter Power
    • Battery Power
    • Solar Power
    • Electric Vehicle Charging
    5b, Jindacheng Industrial Park, Shajing Central Road, Baoan District, Shenzhen, Guangdong, China
    sales@upsen.net
    +86 - (0)755 - 29610051
    +86 - (0)755 - 27807701
    Connect with us through the following social media platforms!
    Copyright © 2016 Shenzhen UPSEN Electric CO., Ltd. All rights reserved.        
    Power by: srl_design