中文版 English
  • Products

    Online UPS Queen Star Series 10K-80KVA

    Power Range: 10K-80KVA (3ph in/3ph out)

    ● DSP + IGBT technology.
    ● Output power factor 0.8.
    ● Active power factor correction in all phases.
    ● Emergency power off function (EPO).

    Where to buy »

    Online UPS Queen Star Series 10K-80KVA  (3ph in/3ph out)


    Key Features

    • True double-conversion.
    • DSP technology guarantees high performance.
    • Output power factor 0.8.
    • Active power factor correction in all phases.
    • 50Hz/60Hz frequency converter mode.
    • Accepts dual-mains inputs.
    • Generator compatible.
    • SNMP+USB+RS-232 multiple communications.
    • 3-stage extendable charging design for optimized battery performance.
    • Adjustable battery numbers.
    • Maintenance bypass available.
    • Optional N+X parallel redundancy.


    User Guides

    User's Manual

    Brochure

    Brochure

    Technical Specification

    Model

    33Q10KL

    33Q 20KL

    33Q 30KL

    33Q 40KL

    33Q 60KL

    33Q 80KL

    Comments

    Input

    Input voltage

    Rated voltage

    380VAC/220VAC

    380VAC

    Phase

    three phase with ground

    Turn on voltage range

    120±5274±5VAC

    207±9475±9VAC

    Bypass voltage range

    60±5300±5VAC

    105±9518±9VAC

    Could be adjusted by software.

    Bypass

    low loss

    60VAC~220VAC(default 60VAC)

    105VAC~380VAC

    (default 105VAC)

    Bypass low comeback

    Low loss +5VAC

    Low loss +17VAC

    Bypass high loss

    220VAC~300VAC(default 300VAC)

    380VAC~475VAC

    (default 475VAC)

    Bypass high comeback

    High loss -5VAC

    High loss -17VAC

    Line low loss

    /comeback

    (120±5) VAC /(140±5) VAC

    (207±9) VAC /(242±9)VAC

    load≤50

    (140±5) VAC /(160±5) VAC

    (242±9) VAC /(276±9)VAC

    50%<load ≤90

    (160±5) VAC /(175±5) VAC

    (276±9) VAC /(302±9)VAC

    load90

    Line high loss/comeback

    (275±5)VAC/(260±5)VAC

    (475±9)VAC/(449±9)VAC

    Input frequency

    Rated frequency

    50Hz

    Frequency

    low loss

    (40~49) ±0.2Hz(default:46Hz)

    Could be adjusted by software.

    Frequency

    low comeback

    Frequency low loss +0.5Hz

    Frequency

    high loss

    (51~60)±0.2Hz(default:54Hz)

    Frequency high comeback

    Frequency high loss -0.5Hz

    Input power factor

    Input power factor

    > 0.99

    33Q 10-40KL:220VAC,full R load

    33Q 60-80KL: 380VAC,full R load

    Generator

    Support generator input

    Generator rating≥2*UPS rating

    Input current

    Rated current

    14A

    28A

    42A

    67A

    80A

    105A

    Input THDI

    <= 10%

    Output protection

    Rating protection

    32A

    Breaker

    50A

    Breaker

    60A

    Breaker

    80A

    Breaker

    100A

    Breaker

    125A

    Breaker

    Output power

    VA/watt

    10KVA/8KW

    20KVA/16KW

    30KVA/24KW

    40KVA/32KW

    60KVA/

    48KW

    80KVA/

    64KW

    Rated voltage

    220VAC

    380VAC

    Sine wave

    Voltage range

    200/208/220/230/240VAC

    345/359/380/397/415 VAC

    33Q 10-40KL: Could be adjusted by software. 10% derating for 208VAC/200VAC.

    33Q 60-80KL: Could be adjusted by software. 10% derating for 345VAC/359VAC.

    Voltage regulation

    ±1%

    Voltage distortion

    ≤5

    ≤10

    Full RCD load

    ≤3

    Full R load

    DC offset

    ≤200mV

    Transient response

    ≤9

    R load 0%~100%~0

    ≤6

    R load 20%~100%~20

    Transient recovery

    ≤60ms voltage recovery to 90%

    Full RCD load

    Bypass output

    before turn-on

    YES

    Crest ration

    3:1

    Output frequency range

    Normal mode

    1,Same as input frequency46Hz~54Hz

    2,50HzInput frequency>54Hz or Input frequency<46Hz)

    Battery mode

    (50±0.1) Hz

    Slew rate

    1 Hz/Sec

    Efficiency

    Normal  mode

    > 93%

    > 90%

    Battery mode

    > 90%

    > 90%

    Overload

    Normal mode

    /battery mode

    Overload warning only

    105%±5%≤load

    1minthen transfer to bypass and alarm.

    105%±5%

    30Sthen transfer to bypass and alarm.

    125%±5%

    300mS, then transfer to bypass and alarm.

    load>150%±5%

    Automatically retransfer

    YES

    Short protection

    Normal/

    battery mode

    YES

    Transfer time

    Normal to battery mode

    0mS

    Battery to normal mode

    0mS

    Normal to bypass mode

    <4mS

    0mS

    Bypass to normal mode

    <4mS

    0mS

    Battery and charger

    Battery

    Rated voltage

    192VDC

    240VDC

    192VDC*2

    192VDC*2

    480VDC

    Type/Rating

    Battery quantity

    16

    20

    16*2

    16*2

    40

    Backup time

    Protection

    Low alarm voltage /comeback voltage

    (180.8V±4V)/ (188.8V±4V)

    (226V±4V)/ (236V±4V)

    (180.8V±4V)/ (188.8V±4V)

    (226V±4V)/ (236V±4V)

    (452V±4V)/ (472V±4V)

    33Q 30KL use two

    Shutdown voltage/ comeback voltage

    160V±4V/168V±4V

    (200V±4V)/ (210V±4V)

    160V±4V/

    168V±4V

    (200V±4V)/ (210V±4V)

    (400V±4V)/ (420V±4V)

    DC protection

    Overcharge protection/ comeback voltage

    (249.6V±4V)/

    (216V±4V)

    (312V±4V) (270V±4V)

    (249.6V±4V)/ (216V±4V)

    (312V±4V) (270V±4V)

    (624V±4V) (540V±4V)

    Leakage current

    < 500uA

    Over discharge protection

    14.5h

    Could be set by software

    Battery test

    Battery weak

    YES

    Battery fault

    YES

    Charger

    Output voltage

    (219.2±3)VDC

    (277±3)VDC

    (219.2±3)VDC

    (277±3)VDC

    (554±3)VDC

    Charge time

    Depends on the external battery capacity

    Charge current

    7.5A

    6A

    5A

    4A

    10A

    Interface

    Alarm silence

    YES

    DC power

    turn-on

    YES

    Automatically retransfer

    YES

    Audio alarm

    Battery mode

    Beep/4s

    Battery low/

    charger fault

    Beep/1s

    UPS fault

    Continue beep

    Overload

    Beep/1s

    Bypass mode

    Beep/2Min

    L/N inverse

    Beep/2Min

    Communication

    RS232 interface

    YES

    Intelligent slot

    YES

    Monitor software

    Appending with UPS

    Cooling

    Force air cooling

    Display

    LCD/LED displays UPS status

    Environment

    Work temperature

    0℃40℃

    Altitude

    1000m

    Audible noise

    ≤60dB

    Storage temperature

    15℃45℃

    Work humidity

    20%95

    Standard

    EMS

    ESD

    IEC61000-4-2

    Level4

    RS

    IEC61000-4-3

    Level3

    EFT

    IEC61000-4-4

    Level4

    Surge

    IEC61000-4-5

    Level4

    EMI

    Conducted

    EN55022

    Class A

    Radiated

    EN55022

    Class A

    Safety

    Safety

    GB4943-2001/IEC62040-1

    Machinery features

    Size

    Outline dimension and net weight

    L*W*H (mm)

    710*260*717

    840*515*1135

    Net weight(Kg)

    45/93

    50/98

    195

    208

    Optional functions

    60Hz

    Optional

    Set by software

    Converter mode

    Optional

    Set by software

    ECO

    Optional

    Optional

    Available and set by software

    EPO

    Optional

    Optional

    *Specification is subject to change without further notice



    Product Category Contact Us UPSEN
    • UPS Power
    • Inverter Power
    • Battery Power
    • Solar Power
    • Electric Vehicle Charging
    1005, Xingji Tower Shangde Rd., Xinqiao St., Bao'an Dist. Shenzhen China
    sales@upsen.net
    +86 - (0)755 - 29610051
    +86 - (0)755 - 27807701
    Connect with us through the following social media platforms!
    Copyright © 2016 Shenzhen UPSEN Electric CO., Ltd. All rights reserved.        
    Power by: srl_design